Gas Boilers - Trinity Lx
GENERAL TRINITY Lx DOWNLOADS
Installation and Operation Manual
Appendix A-Controller & Touchscreen Display
Appendix B-Boiler Applications
Appendix C-Water Heater Applications
Sales Literature
Directives d'installation et de fonctionnement
Cleaning and Service Procedure
TRINITY LX ENGINEERING SUGGESTED SPECS
Trinity Lx150 ASME (R2)
Trinity Lx200 (R2)
Trinity Lx300 (R2)
Trinity Lx400 (R2)
Trinity Lx500 (R2)
Trinity Lx600 (R2)
Trinity Lx700 (R2)
Trinity Lx800 (R2)
SUBMITTALS:
Trinity Lx150E Submittal
Trinity Lx150 ASME
Trinity Lx150 Submittal
Trinity Lx200 Submittal
Trinity Lx300 Submittal
Trinity Lx400 Submittal
Trinity Lx500 Submittal
Trinity Lx600 Submittal
Trinity Lx700 Submittal
Trinity Lx800 Submittal
Trinity Lx Water Heater Submittal
FEATURES
- 5.7” touchscreen display with easy-to-read format, high level of controllability and customization (by both user and installer), Modbus communication, array of software features, and extensive diagnostic and troubleshooting functions.
- Efficiencies of up to 98% steady state and 97% AFUE, and savings of up to 25%
- Maximum permissible modulation rates of 5:1
- Can lead to a reduction of 2.5 tons of greenhouse gases, equivalent to two acres or 280 trees
- Floor or wall-mount configuration
- Factory-installed condensate trap with no moving parts
- Spark ignition with dual electrodes using a high-output transformer
- Removable door and hinged display panel for ultimate serviceability
- No clearance required on the back, bottom or right side
- Three configurable pump outputs
- Integrated combustion platform (ICP)
- Plug-In-Module card contains model specific information; can be used to upload/download custom settings
- All operations are performed in one electronic controller
- Sliding electrical box makes servicing easy
- Critical components are independently fused for superior protection
- Multiple inputs and outputs for ultimate controllability
- Accepts modulation input from other energy management controllers
- Quick connectors allow for easy diagnostics
- High-capacity spark ignition generator
GENERAL SPECIFICATIONS:
| DESCRIPTION |
Lx150 |
Lx150E |
Lx200 |
Lx300 |
|
CSA Input Modulation¹
btu/hr (kw)
|
30,000-150,0002
(8.8-44.0) |
30,000-150,000
(8.8-44.0) |
40,000-199,900
(11.7-58.3) |
55,000-275,000
(16.1-80.5) |
DOE Heating Capacity1,3
btu/hr (kw) |
136,000
(39.8) |
139,000
(40.7) |
182,000
(53.3) |
251,000
(73.5) |
Net I=B=R Rating1,3
btu/hr (kw) |
118,000
(34.8) |
121,000
(35.4) |
158,000
(46.3) |
213,000
(62.4) |
| DOE AFUE3% |
95.1 |
97.0 |
95.1 |
95.1 |
Recovery Rating @
100°F Rise, gal/hr |
- |
- |
224 |
310 |
| Water Connections-NPT, in |
14 |
1 |
1 |
1-1/4 |
| Gas Connection-NPT, in |
1/2 |
1/2 |
1/2 |
1/2 |
Vent/Air-Intake, Pipe Dia
respectively, in. (mm)5 |
37 or 4
(76 or 102) |
37 or 4
(76 or 102) |
37 or 4
(76 or 102) |
4 or 6
(102 or 152) |
Vent/Air Intake,
Max. Length, ft. (m) |
1057
(32) |
1057
(32) |
1057
(32) |
100
(30.5) |
Dimensions HxWxD
in. (mm) |
29.5x17x18.5
(749x432x470) |
29.5x17x18.5
(749x432x470) |
29.5x17x18.5
(749x432x470) |
36x17x21.5
(915x432x546) |
Approx. Appliance Weight
with water, lbs (kg) |
100 (45.3) |
125 (56.7) |
125 (56.7) |
180 (81.6) |
| Electrical Ratings |
120V/1 phase/60 hz/12A |
SPECIFICATIONS Lx400-800
| DESCRIPTION |
Lx400 |
Lx500 |
Lx6006 |
Lx7006 |
Lx8006 |
CSA Input Modulation1
btu/hr (kw) |
75,000-399,000
(21.9-117) |
100,000-500,000
(29.3-146) |
120,000-600,000
(35.1-176) |
160,000-700,000
(46.9-205) |
160,000-800,000
(46.9-234) |
Heating Capacity1
btu/hr (kw) |
374,000
(109.6) |
468,000
(137) |
562,000
(164) |
655,000
(192) |
749,000
(219.5) |
| Steady State Efficiency Rating % |
94.0 |
94.0 |
94.0 |
94.0 |
94.0 |
Recovery Rating @
100°F Rise, gal/hr |
450 |
564 |
677 |
789 |
902 |
| Water Conections-NPT, in. |
1-1/4 |
2 |
2 |
2 |
2 |
| Gas Connection-NPT, in |
3/4 |
3/4 |
1 |
1 |
1 |
Vent/Air Intake Pipe Dia.
respectively, in. (mm)5 |
4 or 6
(102 or 152) |
49 or 6
(102 or 152) |
49 or 6
(102 or 152) |
48 or 6
(102 or 152) |
48 or 6
(102 or 152) |
|
Vent/Air Intake,
Max. Lenght, ft (m)
|
100
(30.5) |
1009
(30.5) |
1009
(30.5) |
100
(30.5) |
100
(30.5) |
Dimensions H x W x D
in. (mm) |
36x17x24
(915x432x610) |
43x17x32.5
(1092x432x825) |
37x17x47.5
(938x432x1206) |
37x17x63.5
(938x432x1613) |
37x17x63.5
(938x432x1613) |
Approx. Appliance Weight
with Water, lbs (kg) |
225 (102) |
320 (145) |
380 (172) |
425 (193) |
475 (215) |
| Electrical Rating |
120V/1 phase/60Hz/12A |
NOTES FOR LX150-800 SPECIFICATIONS:
1 Listed Input and Output ratings are at minimum vent lengths at sea level. Numbers will be lower with lower venting and/or altitudes greater then 2000 feet (610m).
2 The maximum output when operating on LP-Gas is limited to 145, 000 Btu/hr (42.5kw)
3 Based on rating plate input capacities, using standard test procedures prescribed by the US Department of Energy.
4 Units sold in Canada are 3/4" NPT.
5 Trinity Lx require a special venting system, use only vent materials and methods detailed in the instructions.
6 Models, Lx600, Lx700 and Lx800 operate with Natural Gas Only.
7 Models Lx150-200, when using 3" venting on LP, max equivalent length=50 feet.
8 Only 6" exhaust vent is permissable for the Lx700 and Lx800. Air intake pipe can be 4" or 6".
9 Models Lx500 and Lx600 are limited to 30'of 4' or 90' of 6' exhaust venting when using the Indoor Combustion Air kit.
|